Weil-McLain Boiler: High fire and low fire combustion check
High fire and low fire combustion check on a Weil-McLain boiler: Check the flame and combustion at both high fire and low fire. Load devices must be able to take the heat so the boiler does not cycle off during adjustment.
Applies to: SVF 500/600 Series 1 boilers, natural gas and LP
How to fix high fire and low fire combustion check: step by step
- Make sure all load devices (control valves, radiators, air handlers) are running so the boiler does not cycle off.
- Enter Manual Test Mode and call for heat.
- Set FORCE RATE to HIGH. Confirm the maximum firing rate matches Table 18 on page 117.
- Look through the flame inspection window. High fire flame should be blue and stable, with orange dots over the burner surface.
- Remove the test port cap on the vent flue adapter and insert a combustion probe (see Figure 68, page 95).
- Test CO2 and CO against Table 16. If not acceptable, adjust the throttle and offset screws (page 99).
- To check natural gas input: run the boiler 10 minutes with other appliances off, time one cubic foot at the meter, and calculate input.
- Set FORCE RATE to LOW. The low fire flame should be stable, uniform orange, and evenly spread over the burner.
- Repeat the combustion test at low fire.
- Set FORCE RATE back to AUTO and press SAVE.
- Reinstall the vent flue cap and confirm it is sealed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 Boiler Manual, p. 98-99. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.