Weil-McLain Boiler: Gas valve throttle screw and offset adjustment
Gas valve throttle screw and offset adjustment on a Weil-McLain boiler: Only for a qualified technician with calibrated combustion instruments. Adjust only when combustion tests call for it. Gas valve outlet pressure is factory set and must not be measured or adjusted in the field.
Applies to: SlimFit SF-550 and SF-750 Series 3
Common causes of gas valve throttle screw and offset adjustment
- High or low fire CO2 outside the Figure 73 range
- Difficulty igniting
- Poor flame stability at low fire
- Combustion noise
- High carbon monoxide readings
How to fix gas valve throttle screw and offset adjustment: step by step
- Force the firing rate to High in Manual test mode and wait for high fire RPM to settle.
- Read CO2. Remove the blue cover on the throttle screw opening.
- If CO2 is high, turn the throttle screw clockwise in small 1/8-turn steps to lower input.
- If CO2 is low, turn the throttle screw counterclockwise in small 1/8-turn steps to raise input.
- Reinstall the blue cover.
- Lock the boiler at low fire and confirm the low fire RPM is correct.
- If low fire is not acceptable, remove the offset cover screw and use a T40 Torx driver. Turn clockwise to raise CO2 and counterclockwise to lower it.
- Reinstall the cover screw, then return the boiler to AUTO and recheck high fire.
- If both fires cannot be brought into range, contact the WM Technologies representative.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit series3 boiler manual, p. 87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.