Weil-McLain Boiler: Gas valve throttle screw adjustment at high fire
Gas valve throttle screw adjustment at high fire on a Weil-McLain boiler: Only a qualified technician with calibrated combustion instruments may adjust the gas valve. Adjust only as needed to reach the CO2 values in the acceptable values table. Propane is especially sensitive.
Applies to: SlimFit Series 2 gas valve
Common causes of gas valve throttle screw adjustment at high fire
- High or low CO2 at high fire
- Difficult ignition, unstable low fire, combustion noise or high CO
How to fix gas valve throttle screw adjustment at high fire: step by step
- Force high fire in Manual test mode and let the boiler stabilise until the high fire RPM is reached.
- Take a CO2 reading.
- Remove the blue cover over the throttle screw opening.
- Make only 1/8 turn adjustments with a 3 mm Allen wrench.
- If CO2 is high, turn the throttle screw clockwise to lower input.
- If CO2 is low, turn the throttle screw counterclockwise to raise input.
- Allow the boiler to stabilise and read again after each adjustment until the target is reached.
- Reinstall the blue cover.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.