Weil-McLain Boiler: Gas valve throttle and offset adjustment

Updated · by Aurora Star Tech Inc.

Gas valve throttle and offset adjustment on a Weil-McLain boiler: Adjust only as needed to meet Table 16. Confirm the correct low fire RPM before touching the offset screw. Adjust in small steps. Only a qualified technician with calibrated combustion instruments should do this.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Gas valves on SVF 500/600 Series 1 boilers

Common causes of gas valve throttle and offset adjustment

  • Difficult ignition
  • Poor flame stability at low fire
  • Combustion noise
  • High CO

How to fix gas valve throttle and offset adjustment: step by step

  1. Take combustion readings at both high and low fire (Figure 71).
  2. At high fire, check blower RPM against Table 18 on page 117.
  3. At high fire, remove the top cover of the gas valve and use a 4 mm Allen wrench on the throttle screw. If CO2 is high, turn clockwise in small steps. If CO2 is low, turn counterclockwise in small steps.
  4. Allow 20 to 30 seconds to stabilize, then read again. Repeat until CO2 is correct and confirm CO is within limits.
  5. Reinstall the gas valve top cover.
  6. At low fire (0%), let the boiler stabilize and confirm RPM against Table 18.
  7. Remove the T40 Torx cap over the offset screw. If CO2 is high, turn the offset screw counterclockwise in very small steps. If CO2 is low, turn it clockwise.
  8. Wait for stabilization (a few minutes), repeat until CO2 is correct and CO is within limits.
  9. Reinstall the T40 Torx cap.
  10. Turn the boiler off and back on, then recheck high and low fire CO2 and CO.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 500/600 Series 1 Boiler Manual, p. 99-100. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.