Weil-McLain Boiler: Gas valve leakage test
Gas valve leakage test on a Weil-McLain boiler: Test each gas valve solenoid separately. Do not connect a manometer to the manual or automatic gas valve, because the blower vacuum can pull fluid into the gas line and damage the valves.
Applies to: SlimFit Series 2 gas valves
How to fix gas valve leakage test: step by step
- Refer to the gas valve manufacturer's test procedure.
- Go to the Valve Test screen on the control.
- Select Open Gas Valve 1 and press enter/save.
- Give a call for heat. The boiler will only open gas valve 1. Test at the tapping P on the valve body.
- End the call for heat once valve 1 has opened.
- Repeat with Open Gas Valve 2, testing at the manual gas valve side tapping.
- Press back to exit the Gas Valve Test screen. Both valves then open on any call for heat.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 83. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.