Weil-McLain Boiler: Gas-tight leak check at high fire
Gas-tight leak check at high fire on a Weil-McLain boiler: The system must be sealed gas-tight to prevent flue gas spillage and CO. Leaks show as vapor on the inspection mirror.
Applies to: Heat exchanger cover plate, condensate dish, vent and air piping
Common causes of gas-tight leak check at high fire
- Loose cover plate joint
- Damaged gasket
- Loose condensate dish or vent adapter joint
- Vent piping seal failure
How to fix gas-tight leak check at high fire: step by step
- Run the boiler at high fire.
- Move an inspection mirror around all heat exchanger cover plate joints at the top of the boiler.
- Check the joints between the condensate dish, vent adapter and vent pipe.
- Check every connection and seam of air and vent piping for gas-tight seals.
- If a leak is found, shut the boiler down immediately.
- Tighten the retaining screws or nuts if possible. Do not overtighten.
- If tightening does not fix it, disassemble the leaking component (see Maintenance section, page 103).
- Inspect gaskets and replace any that are damaged.
- Contact WM Technologies Technical Services if the problem is not solved.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 Boiler Manual, p. 100-101. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.