Weil-McLain Boiler: Gas supply piping connection and sizing
Gas supply piping connection and sizing on a Weil-McLain boiler: Install a union for servicing when required and a manual shutoff within 6 ft of the boiler, identified by the installer in Canada. Support gas piping with hangers, not the boiler. Size the supply from the meter outlet using the total connected input in Btuh divided by 1,000 for approximate cubic feet per hour, plus fitting equivalent lengths. Manifolded multiple boiler supplies need a manual shutoff, union and sediment trap at each boiler.
Applies to: SlimFit SF1000, SF1500, SF2000
How to fix gas supply piping connection and sizing: step by step
- Install a union for servicing if required.
- Install a manual shutoff valve within 6 ft of the boiler.
- Support the gas piping independently of the boiler and its accessories.
- Divide total connected input in Btuh by 1,000 to get approximate cubic feet per hour.
- Size the supply pipe using the gas capacity table and equivalent fitting lengths.
- On manifolded supplies, add a manual shutoff, union and sediment trap at each boiler, with the trap at least 3 in below the tee.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 45, p. 46. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.