Weil-McLain Boiler: Gas leak check and inlet pressure check
Gas leak check and inlet pressure check on a Weil-McLain boiler: Confirm gas supply pressure at the gas valve test port and check for leaks safely.
Applies to: SVF 500/600 gas supply and gas valve test port
How to fix gas leak check and inlet pressure check: step by step
- Purge all air from the gas supply piping.
- Check the boiler and its gas connection for leaks before starting the boiler. Use a soapy water bubble test only. Never use an open flame.
- For pressure tests below 14 in W.C., close the manual main shut-off valve.
- For pressure tests above 14 in W.C., disconnect the boiler gas connection from the supply piping.
- Connect a manometer or pressure gauge to the tapping on the gas line elbow by the gas valve (Figure 54, p. 63).
- With all gas appliances running, verify minimum pressure at high fire during startup: at least 3.5 in W.C. with gas flowing.
- Confirm the maximum supply pressure is 14 in W.C., whether the boiler is running or off. Install a lock-up regulator if needed (p. 62).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 63. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.