Weil-McLain Boiler: Flow outside Table 5 range

Updated · by Aurora Star Tech Inc.

Flow outside Table 5 range on a Weil-McLain boiler: Do not size piping for flow above or below the Table 5 range without using a suitable piping strategy. Too little flow causes nuisance limit outages. Too much flow can erode the heat exchanger.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Boiler loop flow design

Common causes of flow outside table 5 range

  • Flow too low causes nuisance limit outages
  • Flow too high causes heat exchanger erosion

How to fix flow outside table 5 range: step by step

  1. If flow is above Table 5, use primary/secondary piping or add a differential pressure bypass valve in a variable primary system.
  2. If flow is below Table 5, use primary/secondary piping.
  3. In variable primary flow, consider a flow switch set at the boiler minimum flow. The variable circulator will raise flow, and the switch will allow the boiler to fire.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 500/600 Series 1 boiler manual, p. 21. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.