Weil-McLain Boiler: Fill condensate trap with water
Fill condensate trap with water on a Weil-McLain boiler: The condensate trap must hold water whenever the boiler runs. If it is dry, flue gas can escape through the condensate drain.
Applies to: SlimFit Series 2 boilers
Common causes of fill condensate trap with water
- Trap not filled at startup
- Trap dry after cleaning or service
How to fix fill condensate trap with water: step by step
- Fill the trap with fresh water through the inspection caps near the flue connection on the piping end.
- To remove the trap, loosen the two stainless steel hose clamps on the flexible coupling.
- Slide the coupling off the 1 inch PVC pipe connected to the trap.
- Loosen the trap inlet connection, remove the trap and flush it.
- Refit the trap, fill it with fresh water, reconnect the coupling and tighten the clamps.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 81. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.