Weil-McLain Boiler: Field wiring: power, circulator and strain relief
Field wiring: power, circulator and strain relief on a Weil-McLain boiler: Turn off power at the service panel before wiring. Use N.E.C. Class 1 wiring and type 105 C wire if replacing original wiring. Bond and ground the boiler per code. Use strain relief at the cabinet knockouts. The 24 V transformer output must not power external devices that are not listed in the manual. The boiler circulator relay on the expansion module is dry contact rated 10 A and needs external 120 VAC supply for the pump.
Applies to: SlimFit SF1000, SF1500, SF2000 field wiring
How to fix field wiring: power, circulator and strain relief: step by step
- Turn off electrical power at the service entrance panel.
- Feed line and low-voltage wiring through the top cabinet knockouts and install strain relief.
- Connect 120 VAC power to the boiler.
- Provide external 120 VAC power for the boiler circulator and wire it through the EP7 terminal, interrupting the pump's hot line.
- Confirm the circulator load is within the 10 A relay rating.
- Do not connect external devices to the 24 V transformer output unless listed in the manual.
- Ground and bond the boiler per code.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.