Weil-McLain Boiler: Expansion tank and water connections
Expansion tank and water connections on a Weil-McLain boiler: General piping rules that apply to every layout on pages 16 to 19.
Applies to: SF-550 and SF-750
How to fix expansion tank and water connections: step by step
- Provide a system expansion tank following the guidelines on p. 14.
- Do not use a closed-type expansion tank when connected to a water heater with an automatic vent.
- Install a union on the boiler supply and return as close to the boiler as possible.
- Place the boiler drain valve at 3/4 inch or larger.
- Strap system supply and return sensors to the lines at least 6 pipe diameters (max 3 ft) from the boiler connection tees.
- Install a P/T gauge on the boiler outlet.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual 550-100-559/0725, pp. 16-19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.