Weil-McLain Boiler: Expansion tank and make-up water

Updated · by Aurora Star Tech Inc.

Expansion tank and make-up water on a Weil-McLain boiler: Size the expansion tank for the boiler and system water volume and temperature (boiler water content is in Table 27, page 142). An undersized tank causes relief valve water loss and excess make-up water, which can eventually fail the boiler. Connect the expansion tank to the air separator only if the separator is on the pump suction side. Put the system fill connection at the same point as the expansion tank connection.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: System expansion and fill

Common causes of expansion tank and make-up water

  • Undersized expansion tank
  • Excess make-up water added through fill valve

How to fix expansion tank and make-up water: step by step

  1. Size the tank for boiler and system water volume and temperature.
  2. Connect the tank to the air separator only if the separator is on the pump suction side.
  3. Install the system fill connection at the same point as the expansion tank connection.
  4. With a diaphragm or bladder tank, install an automatic air vent on top of the air separator.
  5. With a diaphragm or bladder tank and boiler above main piping, install an automatic air vent at the top of the outgoing boiler piping.
  6. Charge a diaphragm or bladder tank to system fill pressure before connecting it.
  7. With a closed-type tank, do not use automatic air vents. Remove any vent on the heat exchanger before operation.
  8. With a closed-type tank, pitch horizontal piping toward the tank at 1 in per 5 ft and connect with at least 3/4 in piping.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 500/600 Series 1 boiler manual, pp. 22-23. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.