Weil-McLain Boiler: Example E – field wiring of master and shadow boilers
Example E - field wiring of master and shadow boilers on a Weil-McLain boiler: Master boiler feeds zones 1 to 3 and the boiler isolation valve. Shadow boiler feeds the DHW circulator or DHW valve, zone 4, the bypass valve and the boiler isolation valve. Sensors go to the terminal blocks J16 and J17 with their commons, and the 120 VAC supply is through the service switch.
Applies to: Example E, master and shadow 2 boilers
How to fix example e - field wiring of master and shadow boilers: step by step
- Wire 120 VAC power and ground to each boiler through the service switch.
- Connect the zone thermostats (W, R, C) to the TT inputs listed in Table 6.
- Connect the boiler isolation valve (Item 17a) to the Primary Valve Control output on each boiler.
- Connect the bypass valve (Item 17b) to the Aux output on the shadow boiler and wire it so it closes when energized.
- Connect the DHW circulator or DHW valve to TT1 on the shadow boiler, and use a relay if its load is above the rating.
- Connect outdoor air, system supply and return sensors to J19 on the master.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Evergreen Series 2 advanced manual, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.