Weil-McLain Boiler: ECO Tec S2 power-up shows wrong model or missing sensor
ECO Tec S2 power-up shows wrong model or missing sensor on a Weil-McLain boiler: On power-up the screen shows the boiler model and lists the sensors it finds.
Applies to: ECO Tec 80/110/150/199 Series 2 heating only
Common causes of eco tec s2 power-up shows wrong model or missing sensor
- Control replaced or reset and set to the wrong boiler model
- Sensor unplugged or bad connection
How to fix eco tec s2 power-up shows wrong model or missing sensor: step by step
- Check the model on the power-up screen. If it is wrong, turn the boiler off and set the correct model (control model setting p.105 or a factory reset).
- If a sensor you expect (outdoor, system supply/return) is not listed, check its wiring and connector, then cycle power.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Power up p.74; Wizard p.78-80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.