ECO Tec S2 manual reset high temperature limit on a Weil-McLain boiler: The control has a manual reset high limit set on the Boiler Settings screen (shown at 200 F on the setting screen in the manual). If boiler water goes over it, the boiler locks out.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec 80/110/150/199 Series 2 heating only

Common causes of eco tec s2 manual reset high temperature limit

  • Low or no water flow through the heat exchanger
  • Circulator not running or air-bound
  • Zone valves closed with no by-pass
  • Limit set lower than the system needs

How to fix eco tec s2 manual reset high temperature limit: step by step

  1. Check the boiler circulator runs and the system is full and purged of air.
  2. Check flow: on direct-connect piping the rise across the heat exchanger at high fire should be about 20 to 35 F, not more.
  3. Zone valve systems need a by-pass pressure regulator unless the pump is protected against dead-heading.
  4. Check the setting under Boiler Settings. It can be lowered for some systems but is a safety setting.
  5. Fix the cause, then reset the control.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Boiler settings screen Figure 20 p.17; Wizard boiler settings p.78-80; Direct connect piping p.47. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.