Weil-McLain Boiler: ECO Tec S2 locked out by an external limit (J20)
ECO Tec S2 locked out by an external limit (J20) on a Weil-McLain boiler: External limits can be wired as manual reset (J20 pins 1-2) or auto reset (J20 pins 3-4). A jumper is fitted from the factory on each pair.
Applies to: ECO Tec 80/110/150/199 Series 2 heating only
Common causes of eco tec s2 locked out by an external limit (j20)
- Device wired on J20 pins 1-2 opened (manual reset lockout)
- Device wired on J20 pins 3-4 opened (auto restart)
- Factory jumper missing
How to fix eco tec s2 locked out by an external limit (j20): step by step
- Find which limit is wired to J20 and why it opened.
- Pins 1-2: boiler goes into manual lockout and the alarm contact on J18 pins 4-5 closes. The limit must close, then reset the control by hand.
- Pins 3-4: boiler stops while the limit is open and restarts on its own 150 seconds after it closes.
- No external limit used: make sure the factory jumpers are still on both pairs.
- The J18 alarm contact closes on manual lockout only (rated 24 VAC or less, 0.5 A or less).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Field wiring F/H p.63-64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.