Weil-McLain Boiler: ECO Tec S2 direct-connect piping: temperature rise too low
ECO Tec S2 direct-connect piping: temperature rise too low on a Weil-McLain boiler: Direct-connect piping (no primary/secondary) only works on the 80/110/150 heating-only models, and the boiler pump must give at least a 20 F rise at high fire.
Applies to: ECO Tec 80/110/150 Series 2 heating only
Common causes of eco tec s2 direct-connect piping: temperature rise too low
- System flow higher than the boiler can take
- System head too high for the built-in circulator
- Zoned with circulators (needs primary/secondary)
How to fix eco tec s2 direct-connect piping: temperature rise too low: step by step
- Measure supply and return at high fire. Rise should be 20 to 35 F depending on model.
- Under 20 F: reduce flow until you get 20 F.
- If the built-in pump cannot meet the system head (Figure 57 p.48), or the system is zoned with circulators, re-pipe primary/secondary.
- Zone valve systems need a by-pass pressure regulator.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Direct connect system piping p.47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.