Weil-McLain Boiler: Direct vent sidewall termination with separate air and vent pipes

Updated · by Aurora Star Tech Inc.

Direct vent sidewall termination with separate air and vent pipes on a Weil-McLain boiler: Termination layout when combustion air and flue are run as separate pipes through the wall.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SF-550 and SF-750 direct vent, sidewall with separate pipes

Common causes of direct vent sidewall termination with separate air and vent pipes

  • Vent elbow turned sideways, causing ice buildup on the building side
  • Air inlet and vent terminations at different heights

How to fix direct vent sidewall termination with separate air and vent pipes: step by step

  1. Set the vent and air terminations as in the left-side configuration unless clearance to grade or snow line cannot be met.
  2. Use the right-side configuration (raised terminations) when extra clearance to grade or snow line is needed.
  3. Make the elbow at the exit opening butt against the outside wall plate.
  4. Point the vent elbow outward or away from the air inlet.
  5. If external pipe is up to 4 ft each for vent and air, brace it no more than 24 in apart.
  6. If external vent or air pipe is longer than 4 ft each, insulate the enclosure and exit the terminations through it.
  7. If pipes extend beyond the wall, install a coupling at the exit opening butted to the outside plate, then continue piping from the coupling.
  8. Keep the air and vent piping within the maximum length in the sidewall piping table, observing the elbow reduction rule.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 39. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.