Weil-McLain Boiler: Direct exhaust vertical termination location
Direct exhaust vertical termination location on a Weil-McLain boiler: Place the vertical vent termination where it will not be damaged by debris, leaves or sediment, and where snow will not block it.
Applies to: Direct exhaust vertical termination, Cat. II and IV
How to fix direct exhaust vertical termination location: step by step
- Keep the termination 12 in minimum above the roof or snow line and no more than 48 in above the roof.
- Add a bird screen to the inlet adapter to keep debris out of the boiler cabinet.
- Route the vent from the boiler so total exposed length stays within the Category IV maximum in the venting table (Figure 22, p. 36).
- For multiple boilers, space each vent termination per the clearance figure (Figure 26).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 Boiler Manual, p. 41. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.