Weil-McLain Boiler: Direct exhaust venting: approved components
Direct exhaust venting: approved components on a Weil-McLain boiler: Direct exhaust uses inside combustion air and a pressurized Category III vent. Every joint must be sealed. Use only a listed 3 inch vent system.
Applies to: CGi-25 to CGi-8
How to fix direct exhaust venting: approved components: step by step
- Choose one listed vent manufacturer: Heat-Fab Saf-T Vent, Metal-Fab CORR/GUARD, Z-Flex Z-Vent, or ProTech FasNSeal.
- Use the vent starter from that same manufacturer. Never mix components from different systems.
- Check maximum run length and elbow count against the vent length table. Do not exceed it. The termination fitting is not counted as an elbow.
- Select all vent components, including the vent starter, from the same manufacturer.
- Minimum run is 2 ft equivalent with two elbows.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 Gas-Fired Water Boiler boiler manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.