Weil-McLain Boiler: Direct exhaust vent termination location
Direct exhaust vent termination location on a Weil-McLain boiler: Locate the vent termination so every clearance is met. Site conditions may require more clearance.
Applies to: CGi-25 to CGi-8
How to fix direct exhaust vent termination location: step by step
- Keep the termination at least 4 ft horizontally from electric meters, gas meters, regulators and relief equipment. Never place it above or below these.
- Place the termination more than 4 ft below or to the side of any door or window.
- Keep it more than 1 ft above grade or the expected snow line.
- Keep it at least 7 ft above a public walkway.
- Keep it 3 ft above any forced air intake within 10 ft.
- Keep it at least 6 ft from adjacent walls and no closer than 5 ft below a roof overhang.
- Keep it well away from trees, shrubs and decorative items.
- Do not terminate in a window well, stairwell, alcove, courtyard or other recessed area.
- Do not terminate above any door or window.
- Do not connect another appliance or multiple boilers to the vent pipe.
- Do not wrap or insulate the vent pipe or fittings.
- Do not extend exposed vent pipe more than 4 ft outside the building.
- Locate or guard the termination to prevent condensate damage and accidental contact.
- Do not run the vent through an exterior wall adjacent to eaves, parapets, balconies or decks.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 Gas-Fired Water Boiler boiler manual, p. 23-24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.