Weil-McLain Boiler: Direct exhaust sidewall vent termination: location and clearances

Updated · by Aurora Star Tech Inc.

Direct exhaust sidewall vent termination: location and clearances on a Weil-McLain boiler: Where the sidewall direct exhaust vent may exit the building. The SF-550 and SF-750 are condensing appliances, so flue products and condensate must be kept clear of people, openings and building surfaces.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SF-550 and SF-750 direct exhaust, sidewall termination

Common causes of direct exhaust sidewall vent termination: location and clearances

  • Termination too close to an air inlet, door, window or building surface
  • Termination in a wind eddy or recessed area where flue products recirculate
  • Exposed vent condensate freezing and blocking the pipe

How to fix direct exhaust sidewall vent termination: location and clearances: step by step

  1. Keep the vent termination at least 6 ft from adjacent walls.
  2. Keep it at least 5 ft below any roof overhang.
  3. Keep it at least 3 ft above any forced air intake within 10 ft.
  4. Keep it at least 48 in below or horizontally from any door, window or other gravity air inlet.
  5. Keep it at least 4 ft horizontally from electric meters, gas meters, regulators, relief valves or other equipment.
  6. Do not terminate above a door or window or under a deck.
  7. Do not terminate over a public walkway or where condensate or vapor could be a nuisance.
  8. Keep the external vent within the maximum length shown in the piping length table.
  9. Use braces no more than 24 in apart on exposed external pipe up to 4 ft long.
  10. If external pipe is longer than 4 ft, enclose it in insulation and bring the termination out through the enclosure.
  11. Point the vent elbow outward, away from the air inlet, not sideways.
  12. Keep the termination out of building corners, window wells, stairwells, alcoves and courtyards.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 32-33. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.