Weil-McLain Boiler: Direct exhaust sidewall termination location
Direct exhaust sidewall termination location on a Weil-McLain boiler: Sidewall terminations must meet the location rules in the code and the clearances in Figure 27.
Applies to: Direct exhaust sidewall termination, Category IV
How to fix direct exhaust sidewall termination location: step by step
- Keep vent and air terminations at least 12 in above grade and snow line.
- Keep a minimum of 4 ft horizontally from electrical meters, gas meters, regulators and relief equipment.
- Do not install the termination above or below meters, regulators or relief equipment.
- Do not terminate above a door or window or above a public walkway, where condensate can freeze or drop on people.
- Avoid locations where wind eddies can recirculate exhaust.
- Check the local gas code (NFPA 54 or CAN/CSA B149.1) for minimum distances to openings and buildings.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 Boiler Manual, p. 43. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.