Weil-McLain Boiler: Direct exhaust boiler room air openings
Direct exhaust boiler room air openings on a Weil-McLain boiler: Size the boiler room openings for combustion and ventilation air when the boiler uses inside air. Openings must also handle the air movement of any exhaust fans in the space.
Applies to: Category IV direct exhaust installations
Common causes of direct exhaust boiler room air openings
- Space under negative pressure from exhaust fans or mechanical ventilation
- Tight construction without outside air openings
How to fix direct exhaust boiler room air openings: step by step
- Use Figure 25 to pick the case that matches the room (with or without other appliances, and single or two openings).
- Size each opening as free area after louver or grille reduction.
- If only one opening is used, it must open directly to outdoors (not to an interior space), have its top within 12 in of the ceiling, and have free area at least equal to the total area of all equipment vent connectors in the space.
- If the space volume is at least 50 cu ft per 1,000 Btuh of total appliance input, no openings are needed, provided the building is not tight construction.
- Example: 1,500 MBH total input needs at least 75,000 cu ft (50 x 1,500).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 30-31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.