Weil-McLain Boiler: Connect gas supply piping and check for leaks

Updated · by Aurora Star Tech Inc.

Connect gas supply piping and check for leaks on a Weil-McLain boiler: Gas piping connection and leak test procedure at the boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SlimFit boiler gas connection

How to fix connect gas supply piping and check for leaks: step by step

  1. Remove the jacket front panel.
  2. Install a union for servicing, which is recommended.
  3. Install a manual shutoff valve in the gas supply within 6 feet of the boiler. In Canada the installer must identify the valve.
  4. Support the piping with hangers, not by the boiler or its accessories.
  5. Purge all air from the gas supply piping.
  6. Use two wrenches: hold the boiler gas connection still with one while tightening with the other.
  7. Check the boiler and its gas connection for leaks with a soapy water bubble test. Never use an open flame.
  8. Use propane-compatible pipe dope sparingly on male threads only.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 48. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.