Weil-McLain Boiler: Connect and leak-test the gas supply piping
Connect and leak-test the gas supply piping on a Weil-McLain boiler: Gas connection work on the 550/750 SlimFit. Support the piping with hangers so the boiler is not carrying the load, and use two wrenches so the boiler gas connection does not turn.
Applies to: SlimFit 550/750 Series 3 boiler
How to fix connect and leak-test the gas supply piping: step by step
- Remove the jacket front panel to reach the gas connection.
- Install a union for service, and a manual shutoff valve in the supply piping within 6 feet of the boiler.
- In Canada, make sure the installer identifies the manual gas valve.
- Purge all air from the gas supply piping.
- Leak-check the boiler and its gas connection before firing. Use a soapy water bubble test only, never an open flame.
- For pressure tests at or below 20 in. w.c., close the manual main shutoff valve.
- For pressure tests above 20 in. w.c., disconnect the boiler gas connection from the supply piping.
- Use pipe dope rated for propane, applied lightly to male threads only so it does not block gas flow.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.