Weil-McLain Boiler: Condensate line – sizing, pump and materials
Condensate line - sizing, pump and materials on a Weil-McLain boiler: Route condensate to drain or pump and keep the line open so it cannot back into the boiler.
Applies to: SVF 500/600 condensate drain and pump
Common causes of condensate line - sizing, pump and materials
- Condensate freezes in the line
- Condensate line is obstructed
- Condensate backs up into the boiler
How to fix condensate line - sizing, pump and materials: step by step
- Use 3/4 in PVC or CPVC pipe to route condensate to a drain or pump.
- If using a pump, select one approved for condensing boilers and furnaces, with an overflow switch.
- Provide an external power source for the pump.
- Size the pump for at least 10 GPH per boiler for both SVF 500 and SVF 600.
- When sizing the pump, include the total load of all SVF boilers connected to it.
- Keep the condensate line unobstructed so condensate flows freely. A frozen or blocked line can back up into the boiler and cause lockout.
- Use PVC and CPVC that meets ASTM D1785, F441 or D2665, with cement and primer to ASTM D2564 or F493. In Canada, use CSA or ULC certified pipe, fittings and cement.
- If local code requires, install a neutralizing filter. Condensate is slightly acidic, about pH 3.2 to 4.5. A Weil-McLain neutralizer kit is listed in the Parts section (p. 131).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.