Weil-McLain Boiler: Condensate drain check (220/299/300/399)
Condensate drain check (220/299/300/399) on a Weil-McLain boiler: On larger models, flue gas smell or escaping flue gas at the condensate drain or tee means the trap is dry. The drain line must also run freely.
Applies to: 220/299/300/399 Series 2
Common causes of condensate drain check (220/299/300/399)
- Dry condensate trap
- Obstructed condensate drain line
How to fix condensate drain check (220/299/300/399): step by step
- With the boiler running, hold fingers in front of the discharge end of the condensate tubing and the open top of the condensate tee. Check for flue gas.
- If flue gas escapes, the trap is dry. Fill it using the test port procedure.
- Slowly pour water into the top of the PVC tee on the side of the boiler. Water should run out the end of the condensate drain line.
- If water does not run out, call a service technician to clean or replace the drain line.
- If the trap runs dry regularly, call a service technician to inspect the boiler and condensate line.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Evergreen Series 2 user's information manual, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.