Weil-McLain Boiler: Combustion air manifold (Category IV, direct vent only)
Combustion air manifold (Category IV, direct vent only) on a Weil-McLain boiler: Several Category IV SVF boilers can share one combustion air duct. Only the air inlet piping may be combined. Vent piping must never be combined.
Applies to: SVF 500/600 Series 1, Category IV, direct vent manifolded air
How to fix combustion air manifold (category iv, direct vent only): step by step
- Size the shared air duct at a minimum of 1 sq in of free area per 2,000 Btuh of total connected boiler input, adjusted for louver restriction.
- Divide the total input in MBH by 2 to get the minimum free area in square inches (example: 3,000 MBH gives 1,500 sq in).
- Keep at least 12 in of clearance from the grade or snow line to the air duct opening.
- Keep a minimum of 3 ft below any vent termination within 10 ft horizontally.
- Do not combine Category IV vent piping. Flue gas leakage and component damage can result.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 Boiler Manual, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.