Weil-McLain Boiler: Combustion air contamination
Combustion air contamination on a Weil-McLain boiler: Chlorine or fluorine compounds in intake air form acids in the vent and boiler, which corrode them and can allow flue gas spillage. Products to avoid include chlorinated cleaners and bleaches, pool chemicals, refrigerant leaks, paint removers, muriatic acid, cements, glues and aerosol sprays containing chloro/fluorocarbons. Areas to avoid include laundry rooms, pools, dry cleaners, beauty shops, auto body shops, refrigeration repair shops and new construction.
Applies to: 110/155/220/299/300/399 Series 2
Common causes of combustion air contamination
- Chlorine or fluorine products in combustion air
- Intake located near laundry, pool or other contaminant sources
How to fix combustion air contamination: step by step
- Make sure the combustion air will not contain any listed contaminants.
- Remove contaminating products from the boiler room immediately.
- If products cannot be removed, or the intake is in a contaminated area, have the combustion air and vent re-piped to another location by a qualified technician.
- If products have been present for a long time, call a qualified service technician to inspect for acid corrosion.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Evergreen Series 2 user's information manual, p. 4, 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.