Weil-McLain Boiler: Combustion air contamination check
Combustion air contamination check on a Weil-McLain boiler: Corrosive contaminants in the boiler room or the combustion air source can damage the burner and heat exchanger. Check the room and the air source before installing, and pipe air from outside if contaminants are present.
Applies to: SlimFit SF1000, SF1500, SF2000 Series 2 boilers
Common causes of combustion air contamination check
- Chlorinated or fluorinated products such as spray cans, waxes, cleaners, pool chemicals, or refrigerant leaks
- Solvents, paint or varnish removers, glues, cements, or adhesives in the air supply
- Drywall and construction dust, or heavy dust and dirt
- Air sources near dry cleaning, pool, metal fabrication, beauty, refrigeration, auto body, plastics, or refinishing areas
How to fix combustion air contamination check: step by step
- For direct exhaust (inside air), confirm the boiler room and combustion air source are free of contaminants.
- For direct vent, run the air inlet pipe so it cannot pull in contaminated air.
- Do not operate the boiler during construction unless the air inlet is piped from a dust-free, contaminant-free area.
- Compare the room against the contaminant list in Figure 21 before deciding on inside air.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.