Weil-McLain Boiler: Close-clearance install: boiler off on manual reset temperature switch

Updated · by Aurora Star Tech Inc.

Close-clearance install: boiler off on manual reset temperature switch on a Weil-McLain boiler: Boilers installed with reduced clearances (alcove, closet, under a counter) use close clearance kit 386-500-050. Its manual reset temperature switch is mounted near the top of the enclosed space and wired in series with the thermostat. If the space gets too hot, the switch opens and the boiler gets no call for heat until it is reset.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers

Common causes of close-clearance install: boiler off on manual reset temperature switch

  • Not enough combustion/ventilation air into the enclosed space
  • Flue pipe or jacket cap problem letting heat build up
  • Burner combustion not set right

How to fix close-clearance install: boiler off on manual reset temperature switch: step by step

  1. Power off before working on the burner or wiring.
  2. Find the manual reset temperature switch near the top of the enclosure and check if it has tripped.
  3. Before resetting, check the two ventilation openings (near top and bottom of the space). Each should be 140 sq. in. per 1 GPH of input.
  4. Check that the jacket cap is on and the flue pipe clearances are kept.
  5. Set the burner with a combustion analyzer: zero smoke, over-fire draft -0.01 to -0.02 in. w.c., CO2 about 13% or less (this line is jumbled in the manual text, check the page).
  6. Reset the switch and run the boiler to design temperature. Watch that it does not trip again.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Close clearance installation, Figures 26-27, p.34. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.