Weil-McLain Boiler: Choosing direct exhaust or direct vent
Choosing direct exhaust or direct vent on a Weil-McLain boiler: Direct exhaust takes combustion air from inside the boiler room, and the air piping is not connected to the air inlet. Direct vent pipes combustion air in from outside. Category II is a negative-pressure vent and requires direct exhaust. Category IV is a positive-pressure vent and can use either method.
Applies to: SVF 500/600 boilers, Category II and Category IV
How to fix choosing direct exhaust or direct vent: step by step
- Direct exhaust: supply combustion air through openings into the boiler room, sized per this manual and code.
- Where the boiler shares a space with other appliances, size the combustion air openings for the combined load of all appliances.
- Direct vent: pipe combustion air from outside, keeping the air inlet away from any source of contamination listed in Table 7.
- Combustion air may be piped individually per boiler, or manifolded (Figure 25, p. 40).
- Combustion and ventilation openings may also be required in boiler room walls per this manual and code.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 Boiler Manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.