Weil-McLain Boiler: Chimney draft venting requirements
Chimney draft venting requirements on a Weil-McLain boiler: Natural draft venting through a vertical vent or chimney, Category I. Vent sizing is a general guide only. Code requirements govern.
Applies to: CGi-25 to CGi-8
How to fix chimney draft venting requirements: step by step
- Inspect the existing chimney before installing. Clean or replace any perforated pipe or lining.
- Use double wall B-vent or a lined chimney approved under NFPA 54 / ANSI Z223.1.
- Extend the chimney at least 3 ft above the roof penetration and at least 2 ft above any building part within 10 ft.
- Do not connect to a mechanical draft system that can run under positive pressure.
- Keep 2 inch clearance from combustibles to the vent pipe.
- Do not use a chimney that serves an open fireplace.
- Keep horizontal runs short and support longer runs with hangers.
- Do not vent into the bottom of the chimney. The vent pipe must not go past the inside wall of the chimney.
- Firestop any vent passing through floors or ceilings.
- Size the vent connector per the vent connector diameter table.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 Gas-Fired Water Boiler boiler manual, p. 18-19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.