Weil-McLain Boiler: Chimney and vent requirements
Chimney and vent requirements on a Weil-McLain boiler: Venting must follow Part 7 of the National Fuel Gas Code and local building codes. A chimney or vent without a listed cap must extend at least 3 feet above the roof penetration and at least 2 feet higher than any building part within 10 feet horizontally. A lined chimney is preferred and required where codes call for it. Cold masonry chimneys can suffer condensation damage with atmospheric boilers. Where two or more gas appliances share a chimney, the combined area should be at least the largest outlet plus 50 percent of each additional outlet. Minimum vent sizes are on the Ratings table (p. 91).
Applies to: CGi-25 to CGi-8
Common causes of chimney and vent requirements
- Condensation damaging a cold masonry chimney
How to fix chimney and vent requirements: step by step
- Confirm the vent or chimney extends at least 3 feet above the roof and 2 feet above any building within 10 feet.
- Inspect the existing chimney or tile liner for cracks and damage before install. Replace perforated or damaged liners.
- On a cold masonry chimney, line it with corrosion-resistant metal such as AL29-4C single-wall stainless or a properly sized B-vent liner.
- Provide a drain trap to remove condensate.
- Size a shared chimney using the largest outlet plus 50 percent of each additional outlet area.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 Gas-Fired Water Boiler Manual, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.