Weil-McLain Boiler: Chilled water system piping (boiler in parallel with chiller)
Chilled water system piping (boiler in parallel with chiller) on a Weil-McLain boiler: The chiller is piped in parallel with the boiler. Valves keep chilled medium out of the boiler.
Applies to: SlimFit 1000-2000 Series 2
Common causes of chilled water system piping (boiler in parallel with chiller)
- Chilled medium entering the boiler
- Gravity circulation through the boiler during cooling
- Wrong antifreeze in the boiler loop
How to fix chilled water system piping (boiler in parallel with chiller): step by step
- Pipe the chiller in parallel with the boiler.
- Install valves that stop chilled medium from entering the boiler.
- If coils in air handlers can see refrigerated air, add flow control valves or other automatic means to stop gravity circulation during cooling.
- Install a closed-type expansion tank for this system (Figure 20, item 15).
- Install a union on the boiler supply and return connections close to the boiler for service.
- Use only antifreeze listed by Weil-McLain for this boiler (see page 105). Consider antifreeze effects on circulator sizing and DHW performance.
- Check local codes, which may require a double-wall DHW heat exchanger.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 Boiler Manual, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.