Weil-McLain Boiler: Checking the limit control on a WTGO boiler
Checking the limit control on a WTGO boiler on a Weil-McLain boiler: The combination limit control (in the tankless heater plate, with low water cut-off) shuts off the burner on high water temperature but lets the circulator keep running while there is a call for heat. Maximum setting is 220°F.
Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers
Common causes of checking the limit control on a wtgo boiler
- Limit set below the temperature the system needs
- Limit control or low water cut-off faulty
How to fix checking the limit control on a wtgo boiler: step by step
- With the burner running, turn the limit indicator below the actual boiler water temperature. The burner should stop and the circulator should keep running.
- Turn the limit back above the water temperature. The burner should light again.
- If the boiler has a low water cut-off, extra high limit or other field controls, test each one the way its maker says.
- Set the limit higher than the temperature the system needs, never above 220°F.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Check-out procedure p.30; System components p.33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.