Weil-McLain Boiler: Checking the boiler out (supply) temperature sensor

Updated · by Aurora Star Tech Inc.

Checking the boiler out (supply) temperature sensor on a Weil-McLain boiler: Resistance-type sensor. Check its value against the reference table and confirm the control reads temperature correctly.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: CGi-25 to CGi-8

How to fix checking the boiler out (supply) temperature sensor: step by step

  1. Measure sensor resistance with an ohmmeter at known temperatures: freezing (32 F), room temp (60-70 F) and boiling at sea level (212 F). For freezing and boiling, put the sensor in water at that temperature.
  2. Compare readings with the sensor resistance table.
  3. To check the control, put a resistance decade box in place of the sensor and confirm the displayed temperature matches the resistance input.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: CGi Series 5 boiler manual, p. 73. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.