Weil-McLain Boiler: Check water system pressure and automatic air vents
Check water system pressure and automatic air vents on a Weil-McLain boiler: Confirm cold fill pressure and control pressure rise during heat-up.
Applies to: SlimFit 550 and 750 Series 3
Common causes of check water system pressure and automatic air vents
- Pressure that rises too far during heat-up points to an expansion tank sizing or performance problem.
How to fix check water system pressure and automatic air vents: step by step
- Confirm all system components are installed correctly and working.
- Check cold fill pressure. It is usually about 12 psig.
- Watch system pressure while the boiler heats up and confirm it does not rise too high.
- Inspect automatic air vents and air separators. Remove the vent caps and briefly press the push valve to flush each vent. Reinstall the caps.
- Replace any vent that leaks.
- Check water chemistry (inhibitor concentration, pH and hardness). See page 83.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 92. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.