Weil-McLain Boiler: Check the limit control and extra high limit (oil water boiler)
Check the limit control and extra high limit (oil water boiler) on a Weil-McLain boiler: How to prove the limit stops the burner, and how the optional second high limit is set.
Applies to: WGO-2 to WGO-9 oil-fired water boilers
How to fix check the limit control and extra high limit (oil water boiler): step by step
- With the burner running, turn the limit setting below the actual boiler water temperature. The burner must stop and the circulator keeps running.
- Turn the setting back above the water temperature. The burner should relight.
- If a second high limit is required (ASME, UL 726 or Canadian rules), it goes in the supply piping between the boiler and the isolation valve.
- Set that second limit at least 20 F above the combination control set point. Max allowed setting is 220 F.
- The combination control must run with thermal pre-purge or thermal targeting on, unless the boiler falls under one of the exemptions printed in the manual.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, High temperature limit p.23; Check-out procedure p.28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.