Weil-McLain Boiler: Check the high flue pressure switch
Check the high flue pressure switch on a Weil-McLain boiler: Confirms the high flue pressure switch trips and the control locks out as expected.
Applies to: SVF 500/600 boilers, flue pressure switch
How to fix check the high flue pressure switch: step by step
- Check that the switch wire connections are secure and the tubes are tight on the pressure ports.
- Inspect the tubes for damage or debris and replace if needed.
- After checking control settings, disconnect the tube at the condensate dish.
- Gently blow into the tube until the high flue pressure switch opens and the control shows a lockout.
- Clear the lockout on the control and confirm it does not come back.
- Reconnect the tube securely to the condensate dish.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 500/600 boiler manual, p. 114. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.