Weil-McLain Boiler: Check the burner flame

Updated · by Aurora Star Tech Inc.

Check the burner flame on a Weil-McLain boiler: Visual flame check at high and low fire, with burner cleaning if the flame is poor.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 500/600 boilers

How to fix check the burner flame: step by step

  1. Look at the burner flame through the observation window at high and low fire (see pages 98-99).
  2. If the flame is poor, check combustion values. If combustion is properly set, turn the boiler off and let it cool.
  3. Remove the burner and clean it with a vacuum or water flush. Do not rub or scrape the fiber mesh when vacuuming.
  4. Let a water-flushed burner dry completely before reinstalling.
  5. Replace the burner gasket when the burner is removed.
  6. Restart the boiler and check the flame again at high and low fire.
  7. If combustion still cannot be set properly, order a replacement burner.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain SVF 500/600 boiler manual, p. 115. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.