Check remaining appliances on old common vent when removing a boiler on a Weil-McLain boiler: Before an SVF boiler replaces an older boiler on a common vent, test each appliance left on that vent, one at a time, to confirm it still vents correctly.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Replacing an existing boiler on a common vent

Common causes of check remaining appliances on old common vent when removing a boiler

  • Removing the old boiler can leave the common vent too large for the remaining appliances

How to fix check remaining appliances on old common vent when removing a boiler: step by step

  1. Seal any unused openings in the common vent.
  2. Inspect the vent for correct size, horizontal pitch, blockage, restriction, leaks, corrosion or other damage.
  3. Close building doors, windows and doors to the appliance space.
  4. Run the clothes dryer, other non-vented appliances and all exhaust fans (except a summer fan) at maximum speed. Close fireplace dampers.
  5. Make sure no other appliance on the common vent is running. Test one appliance at a time.
  6. Light the appliance under test and run it continuously for five minutes.
  7. Check for spillage at the draft hood relief opening using a flame, or smoke from a cigarette, cigar or pipe.
  8. Return doors, windows, fans, dampers and other appliances to their previous state.
  9. If the vent does not work correctly, correct it to the National Fuel Gas Code (ANSI Z223.1/NFPA 54), or CAN/CSA B149.1 in Canada. When resizing, use the code tables and approach the minimum size.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 500/600 series 1 boiler manual, p. 32. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.