Weil-McLain Boiler: Check manifold orifice sizing
Check manifold orifice sizing on a Weil-McLain boiler: Confirm the burner orifices match the gas type and altitude before firing. The size is stamped on the orifice spud barrel.
Applies to: CGi-25 to CGi-8
How to fix check manifold orifice sizing: step by step
- Remove the front jacket door.
- Remove the burner shield (see parts page 84).
- Read the orifice size stamped on the spud barrel and compare it to the orifice sizing table.
- Use only correctly sized manifold orifices.
- Reinstall the burner shield. Never run the boiler without it.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 Gas-Fired Water Boiler boiler manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.