Weil-McLain Boiler: Check flame and combustion at high and low fire
Check flame and combustion at high and low fire on a Weil-McLain boiler: Combustion is checked with calibrated instruments at high fire and low fire, with the firing rate forced in Manual test mode.
Applies to: SlimFit SF-550 and SF-750 Series 3
How to fix check flame and combustion at high and low fire: step by step
- Call for heat from one heat demand input.
- Press and hold the UP and DOWN arrow keys for five seconds to open the installer menus.
- Go to DIAGNOSTICS and then Manual test mode, and force the firing rate to High.
- Check that the high fire flame is blue and stable and the burner surface has orange dots.
- Pull the flue temperature sensor and insert a calibrated combustion test probe.
- Measure CO2 (or O2) and CO. CO2 must be within 1.0% of the Figure 73 values.
- Set the firing rate to Low and repeat the flame check and combustion test.
- Set the firing rate back to AUTO.
- Reinstall the flue gas temperature sensor before leaving the boiler.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit series3 boiler manual, p. 86. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.