Weil-McLain Boiler: Check control module and expansion module fuses
Check control module and expansion module fuses on a Weil-McLain boiler: Check fuses before replacing the control module or major components such as the blower. A blown fuse can stop the control or other components.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of check control module and expansion module fuses
- Blown low voltage control fuse
- Blown line voltage control fuse
- Blown expansion module fuse
How to fix check control module and expansion module fuses: step by step
- Turn OFF power to the boiler at the external line switch.
- Remove the jacket top panel to expose the control module and expansion module.
- Remove and inspect the two control fuses and the expansion module fuse.
- If replacing a fuse: low voltage fuse (item 1) is a 3 amp fast-blow, Littelfuse 0287003. Line voltage fuse (item 2) is a 12 amp fast-blow, Littelfuse 0314012 MXP or Bussman ABC-12-R.
- Never jumper a fuse or use any fuse other than the specified type.
- Reinstall the jacket top panel and jacket door.
- Restore power at the external line switch and verify operation.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 94. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.