Weil-McLain Boiler: Check burner flame at high fire and low fire
Check burner flame at high fire and low fire on a Weil-McLain boiler: Judge flame quality through the observation window at both firing rates.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of check burner flame at high fire and low fire
- Fouled or damaged burner surface
- Air/fuel imbalance
- Dirty or obstructed burner
How to fix check burner flame at high fire and low fire: step by step
- View the flame through the observation window while performing the startup procedure on pages 82 to 85.
- High fire: flame should be blue and stable, with the burner surface covered in orange dots.
- Low fire: flame should be stable, spread evenly over the burner surface, and uniform orange in color.
- If the flame is poor at high or low fire, perform the testing on page 82. If the problem remains, shut down and let the boiler cool, then remove and clean the burner.
- Retest the boiler after cleaning and confirm the flame is acceptable.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 91. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.