Weil-McLain Boiler: Check blower speeds at low, medium and high fire
Check blower speeds at low, medium and high fire on a Weil-McLain boiler: Compare blower RPM at each firing rate against the reference table. Altitude setting affects this check.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of check blower speeds at low, medium and high fire
- Blower speed out of range
- Incorrect altitude setting
How to fix check blower speeds at low, medium and high fire: step by step
- For installs above 5,500 ft, set the high altitude option in the boiler setup menu. The control adjusts low fire and ignition rates automatically.
- For installs below 5,500 ft, do not enable high altitude.
- Go to Manual Test Mode on the control display.
- Set firing rate to Low. Write down the RPM and compare with the table in Figure 74 on page 82. Low fire rate is adjusted in the boiler setup menu.
- Set firing rate to MEDIUM (ignition rate). Write down RPM. It should be within 200 RPM of the table value.
- Set firing rate to High. Write down RPM. It should be within 200 RPM of the table value.
- If any value is outside these ranges, contact the factory for technical assistance.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 92. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.