Weil-McLain Boiler: Check blower speeds at low fire, ignition and high fire
Check blower speeds at low fire, ignition and high fire on a Weil-McLain boiler: Compares blower RPM with the altitude tables for the installed fuel and altitude.
Applies to: SVF 500/600 boilers
How to fix check blower speeds at low fire, ignition and high fire: step by step
- Above 2,000 ft, confirm the control is set up for the correct blower RPM for low fire and ignition.
- Navigate to Manual Control Firing Rate on the display (SVF Advanced Manual, part 550-100-207).
- Set the firing rate to 0% (low fire) and record the blower RPM.
- Compare the RPM with Table 18. It should not be below the minimum setting or above the ignition factory setting.
- Set the firing rate to 100% (high fire) and record the RPM.
- The high fire RPM should be within 200 RPM of the Table 18 value.
- If any value is outside these ranges, contact WM Technologies technical assistance.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 500/600 boiler manual, p. 116. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.